GEHP-93
             
 
 
ENGINE
Manufacturer Perkins
Model 1004-TG
Power 120cv (1800rpm) | 67hp (1500rpm)
Cylinder 4 in-line
Displacement 4 litres (100 x 127mm)
Compression 16 : 1
Aspiration Turbocharged
Combustion

Direct injection

Consumption 17.9 l/h (60Hz) | 14.8 l/h at 100% load
Cooling System Water cooling
Filters Air, fuel and oil
DC System 12V cc (with batery included), alternator and charger
Panel RPM, hour meter, coolant temperature, oil pressure, manual start
Protection Engine stopped with overheating and low oil pressure
 

 

ALTERNATOR
Manufacturer Heimer
Model ATED
Type Synchonous, brushless, 4 poles, 12 leads 3 phase or single phase (optional)
Connection Star with accesible neutral
Regulation Electronic voltage regulation within 2%
Cooling System Shaft mounted fan
Isolation Class "H"
Bearings Single or double bearing (availiable under consult)

POWER
Stand By 93 kVA - 74 kW / 60 Hz 74 kVA - 59 kW / 50 Hz
Prime 85 kVA - 68 kW / 60 Hz 67 kVA - 54 kW / 50 Hz

DIMENSIONS
Open Set 2130mm L x 900mm W x 1460mm H
Silent Set 3600mm L x 1100mm W x 1830mm H

Base: steel base MIG welded with rubber feet for engine and alternator support for use during about 8 hours. (May be supplied separatelly if requested).

Silent Enclosure: (optional) Soundproofed to 75dB at 7m or 85dB at 1.5m

AUTOMATIC SWICHBOARD
Equipped with microprocessed modules of start and stop control and monitoring of engine protection variables.

Accessories included: Muffler, flexible connection and vibra-stops.
Technical, operation and maintenance manuals, electrical diagrams.

* Pictures for illustrations only.

 

 
            
Leon Heimer - +55 81 3372 8888 - geradores@heimer.com.br