GEHP-1656
             
 
 
ENGINE
Manufacturer Perkins
Model 4012-46TAG2A
Power 0hp (1500rpm)
Cylinder 12 V at 60°
Displacement 30.8 litres (160 x 190mm)
Compression 13.6 : 1
Aspiration Turbocharged
Combustion

Direct injection

Consumption 0 l/h (60Hz) | 0 l/h (50Hz) at 75% load
Cooling System Radiator and fan
Filters Air, fuel and oil
DC System 12V cc (with batery included), alternator and charger
Panel RPM, hour meter, coolant temperature, oil pressure, manual start
Protection Engine stopped with overheating and low oil pressure
 

 

ALTERNATOR
Manufacturer Heimer
Model ATED
Type Synchonous, brushless, 4 poles, 12 leads 3 phase or single phase (optional)
Connection Star with accesible neutral
Regulation Electronic voltage regulation within 2%
Cooling System Shaft mounted fan
Isolation Class "H"
Bearings Single or double bearing (availiable under consult)

POWER
Stand By 1656 kVA - 1325 kW / 60 Hz  
Prime 1505 kVA - 1204 kW / 60 Hz  

DIMENSIONS
Open Set 5200mm L x 1900mm W x 2500mm H
Silent Set 6060mm L x 2438mm W x 2590mm H

Base: steel base MIG welded with rubber feet for engine and alternator support for use during about 8 hours. (May be supplied separatelly if requested).

Silent Enclosure: (optional) Soundproofed to 75dB at 7m or 85dB at 1.5m

AUTOMATIC SWICHBOARD
Equipped with microprocessed modules of start and stop control and monitoring of engine protection variables.

Accessories included: Muffler, flexible connection and vibra-stops.
Technical, operation and maintenance manuals, electrical diagrams.

* Pictures for illustrations only.

 

 
            